Table · ABCB Housing Provisions 2025

Table 11.3.6c Continuous wire barrier construction — Minimum required tension (N) for vertical or near-vertical stainless steel wires where the maximum clear spacing between the rails is 900 mm

Part 11.3 Barriers and handrails

Open Table 11.3.6c on NCC Online ↗
Wire dia. (mm)LayWire spacing (mm)Required tension in Newtons (N)
2.57 x 1980145
100310
110610
2.57 x 780130
100280
110500

Table Notes

Lay = number of strands by the number of individual wires in each strand. For example a lay of 7 x 19 consists of 7 strands with 19 individual wires in each strand.

Vertical wires must have two pulley blocks to each 180 degree change of direction in the wire.

Near vertical wires may only require one pulley block for each change of direction.

Wire tension measured with a strain indicator.

The table only includes 7 x 7 and 7 x 19 wires due to other wires not having sufficient flexibility to make the necessary turns.

Table for 11.3.6 Construction of wire barriers

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 11.3.6c.