Table · ABCB Housing Provisions 2025

Table 4.2.13g Minimum dimensions of circular and square pad footings for clad frame, Class A and S sites

Part 4.2 Footings, slabs and associated elements

Open Table 4.2.13g on NCC Online ↗
Effective supported areas (m2)Width of square pad (mm)Width of circular pad (mm)Thickness (t) (mm)Depth (mm)
10400500200400
20500600200400
30600750250400

Table Notes

The effective area supported by a pad footing is the sum of—

the supported floor area; and

the supported roof area (if applicable); and

half the supported wall area in elevation (if applicable).

The width or diameter can be reduced to one half the above footings on rock.

The pad footings must be constructed in concrete.

Pad footing sizes must also apply to footings supporting roof and floor loads only.

The foundation must provide an allowable bearing pressure of not less than 100 kPa.

The excavation must be backfilled with manually rodded tamped soil, or the footing thickness shall be increased by 50 mm.

Where stump pad footings provide resistance to horizontal or uplift forces, the minimum size of the footing must comply with AS 2870.

Braced stumps must comply with 4.2.13(5).

For masonry piers, strip footings complying with 4.2.15 for masonry can be used in lieu of pad footings.

Table for 4.2.13 Stump footing details

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 4.2.13g.