Table · ABCB Housing Provisions 2025

Table 4.2.15c Dimensions and reinforcement for strip footing systems for Class M sites

Part 4.2 Footings, slabs and associated elements

Open Table 4.2.15c on NCC Online ↗
Type of constructionD (mm)B (mm)Reinforcement (top and bottom)
Clad frame4003003-L11TM
Articulated masonry veneer4503003-L11TM
Masonry veneer5003003-L12TM
Articulated full masonry6004004-L12TM
Full masonry900 Note 24004-L12TM

Table Notes

All masonry walls must be supported on strip footings.

For beams 700 mm or deeper, as specified in the table above, internal footings must be provided at no more than 6 m centres and at re-entrant corners to continue footings to the opposite external footing. Internal strip footings must be of the same proportions as the external footings and run from external footing to external footing. ‘Side slip joints’ consisting of a double layer of polyethylene must be provided at the sides of the footing only.

Infill floors must only be used for Class A and S sites.

Where footings are wider than the specified width, an extra bottom bar or equivalent of the same bar size is required for each 100 mm additional width. If strip footings deeper than those required are used, the reinforcement must be increased to match that specified for the deepened proportions.

The measurement of Df is greater or equal to D plus 75 mm.

Alternative reinforcing sizes must comply with AS 2870.

For Class M articulated full masonry and full masonry, internal strip footings must be of the same proportions as the external footing and run from external footing to external footing.

Table for 4.2.15 Strip footings Class A, S and M sites

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 4.2.15c.