WA 13.2.7 Attached Class 10a buildings, and floors of upper storeys of Class 1 buildings projecting beyond the external walls of the ground floor
WA Part 13.2 Building fabric · varies 13.2.7 Attached Class 10a buildings
Delete clause 13.2.7 and insert WA 13.2.7 as follows:
(1) A Class 10a building attached to a Class 1 building must—
have an external fabric that achieves the required level of thermal performance
for a Class 1 building; or
be separated from the Class 1 building with construction
having the required level of
thermal performance for the Class 1 building.
(2) Where the floor of a Class 1 building is providing separation for the purpose of 13.2.7(1)(a) it must—
in climate zone 4 be insulated with reflective insulation facing down with a minimum
R-Value of 2.0.
in climate zone 5 be insulated with reflective insulation facing down with a minimum
R-Value of 2.5.
(3) The floor of an upper storey of a Class 1 building which has a conditioned space above and projects beyond external walls of the ground floor must, for the extent that it projects beyond the external walls—
in climate zone 4 be insulated with reflective insulation facing down with a minimum
R-Value of 2.0.
in climate zone 5 be insulated with reflective insulation facing down with a minimum
R-Value of 2.5.