Western Australia variation · ABCB Housing Provisions 2025

WA 13.2.7 Attached Class 10a buildings, and floors of upper storeys of Class 1 buildings projecting beyond the external walls of the ground floor

WA Part 13.2 Building fabric · varies 13.2.7 Attached Class 10a buildings

Open on NCC Online ↗

Delete clause 13.2.7 and insert WA 13.2.7 as follows:

(1) A Class 10a building attached to a Class 1 building must—

have an external fabric that achieves the required level of thermal performance

for a Class 1 building; or

be separated from the Class 1 building with construction

having the required level of

thermal performance for the Class 1 building.

(2) Where the floor of a Class 1 building is providing separation for the purpose of 13.2.7(1)(a) it must—

in climate zone 4 be insulated with reflective insulation facing down with a minimum

R-Value of 2.0.

in climate zone 5 be insulated with reflective insulation facing down with a minimum

R-Value of 2.5.

(3) The floor of an upper storey of a Class 1 building which has a conditioned space above and projects beyond external walls of the ground floor must, for the extent that it projects beyond the external walls—

in climate zone 4 be insulated with reflective insulation facing down with a minimum

R-Value of 2.0.

in climate zone 5 be insulated with reflective insulation facing down with a minimum

R-Value of 2.5.

New in NCC 2025. No WA 13.2.7 in ABCB Housing Provisions 2022; it may have moved or been renumbered.

The national clause