B4P3 Isolation
Part B4 Fire-fighting water services
(1) A means of isolation must be provided to a fire-fighting water service and components that require testing, maintenance or replacement, including mechanical devices and controls.
(2) Adequate drainage must be provided for flow testing of fire-fighting water services.
Changed since NCC 2022. See NCC 2022 Volume Three B4P3, or show what changed.
Water storage supplying fire-fighting systems (1) A means of isolation must be sized suitably provided to a fire-fighting water service and components that require testing, maintenance or replacement, including mechanical devices and controls. (2) Adequate drainage must be provided for the level flow testing of risk and supply arrangements. fire-fighting water services.
Removed words are struck through; added words are highlighted. Comparison of the text only.