S1C3 FRLs determined by calculation
Specification 1 Fire-resistance of building elements · NCC 2019: Sch. 5: 3
If the FRL of a building element is determined by calculation based on a tested prototype—
the building element may vary from the prototype in relation to—
length and height if it is a wall; and
height if it is a column; and
span if it is a floor, roof or beam; and
conditions of support; and
to a minor degree, cross-section and components; and
the report must demonstrate by calculation that the building element would achieve the FRL if it is subjected to the regime of the Standard Fire Test in relation to—
structural adequacy (including deflection); and
integrity; and
insulation; and
the calculations must take into account—
the temperature reached by the components of the prototype and their effects on strength and modulus of elasticity; and
appropriate features of the building element such as support, restraint, cross-sectional shape, length, height, span, slenderness ratio, reinforcement, ratio of surface area to mass per unit length, and fire protection; and
features of the prototype that influenced its performance in the Standard Fire Test although these features may not have been taken into account in the design for dead and live load; and
features of the conditions of test, the manner of support and the position of the prototype during the test, that might not be reproduced in the building element if it is exposed to fire; and
the design load of the building element in comparison with the tested prototype.