Specification clause · NCC 2025 Volume Three
S2C25 Reinforcing for column and beam protection — structural concrete and poured gypsum
Specification 2 Descriptions of elements referred to in Specification 1 · NCC 2019: Sch. 5 (Annex): 11.3
If a steel column or a steel beam is to be protected with structural concrete or poured gypsum, the concrete or gypsum must be reinforced with steel-wire mesh or steel-wire binding placed about 20 mm from its outer surface, and—
for concrete or gypsum less than 50 mm thick, the steel wire must be—
at least 3.15 mm in diameter; and
spaced at not more than 100 mm vertically; or
for concrete or gypsum not less than 50 mm thick, the steel wire must be either—
of a diameter and spacing in accordance with (a); or
at least 5 mm in diameter and spaced at not more than 150 mm vertically.
Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three S2C25.