Table · NCC 2025 Volume Three

Table B5V1d Cross-connection type

Part B5 Cross-connection control

Open Table B5V1d on NCC Online ↗
Site conditionCommon examplesNotesScore
The product or installation presents no possibility of cross-connection to food, drink or water or other liquid vessels other than those used for domestic purposes.Residential units and offices.There are no water storage tanks, swimming pools, spas or commercial kitchens on site or able to be installed.0
The product or installation presents a potential for a cross-connection between a drinking water service and a commercial food, drink or water or other liquid vessel, or any vessel intended for low hazard chemicals.Small scale food processing facilities.Potential backflow from low volume of non-hazardous substances. Non-hazardous chemicals are any substances not required to display a hazardous substance label.1
The product or installation presents a potential for a cross-connection between a drinking water service and a non-drinking water service.Drinking water outlets within close proximity to an alternative water source such as a Network Utility Operator drinking water supply, bore or irrigation system.Potential connection of a drinking water system and a system identified with a Low Hazard.2
The product or installation presents a potential for cross-connection between the drinking water service and a swimming pool, water storage tank used for commercial purposes, large scale food and drink processing operations, a vessel, pipe or body of liquid containing a hazardous substance or Schedule 5 poison, recycled water service with biological matter or faecal contamination.Building header tanks, commercial swimming pool make up water connections, soft drink manufacturers.Potential connection of a drinking water system and a system containing an hazardous substance or low toxicity poison or large quantities of food or drink product. Hazardous chemicals are any substances required to display a hazardous substance label.3
The product or installation presents the potential for cross-connection between the drinking water service and a bulk water service vessel containing a hazardous substance or Schedule 5 poison.Chemical make-up water connected to a chemical batching process.Any potential connection to a system containing large volumes of hazardous material or moderately poisonous material.4
The product or installation has potential for a cross-connection to a sewerage source, a trade waste source, a vessel with human or animal biological or faecal matter, a vessel pipe or body of liquid containing any quantity of a Schedule 1 to 4 or Schedule 6 to 8 poison.Recycled water irrigation system with drinking water back up supply.Applies to potential connections with a high health risk.5

Table for B5V1 Determination of individual and zone hazard ratings

Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three Table B5V1d.

Defined terms used