Table S1C2e FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on not more than 3 sides

Specification 1 Fire-resistance of building elements

Open Table S1C2e on NCC Online ↗
Fire protectionMinimum thickness (mm) of principal material for FRLs
60/60/6090/90/90120/120/120180/180/180240/240/240
Concrete cast in-situ — load bearing2530405575
Concrete cast in-situ — non-load bearing unplastered2530405075
Concrete cast in-situ — non-load bearing plastered 13 mm2525304050
Gypsum cast in-situ----50
Gypsum — perlite or gypsum-vermiculite plaster—sprayed to contour2025355055
Gypsum — perlite or gypsum-vermiculite plaster—sprayed on metal lath2020253545

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table for S1C2 Rating

Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three Table S1C2e.