Table · NCC 2025 Volume Three

Table S2C26b Reinforcement of gypsum-perlite or gypsum-vermiculite plaster sprayed to contour — vertical members with other shapes

Specification 2 Descriptions of elements referred to in Specification 1

Open Table S2C26b on NCC Online ↗
Surface to be protectedReinforcement required if smaller dimensions of surface exceeds (mm)Max spacing of fixings of the mesh to surface (mm)
VerticalAny size450
Non-verticalAny size300
UndersizeAny size300
Upper side of a horizontal surfaceNot requiredN/A

Table for S2C26 Reinforcing for column and beam protection — gypsum-perlite or gypsum-vermiculite plaster sprayed to contour