Tasmania variation · NCC 2025 Volume Three

TAS C2D6 Venting requirements

TAS Part C2 Sanitary drainage systems

Open on NCC Online ↗

Insert TAS clause C2D6 in clause C2D6 as follows:

(1) A sanitary drainage system must provide ventilation in accordance with AS/NZS 3500.2.

(2) A sanitary drainage system which connects to an on-site wastewater management system must have—

a secondary vent within 10 metres of the on-site wastewater management system; or

where (a) cannot be achieved, a low level (ground) vent at the sanitary drainage point of connection.

(3) A sanitary drainage system which connects to an on-site wastewater management system must have inspection openings that—

are located at the point of connection to an on-site wastewater management system; and

terminate at or above finished surface level.

Changed since NCC 2022. See NCC 2022 Volume Three TAS C2D6, or show what changed.