TAS C4D12 Grease interceptors

TAS Part C4 On-site liquid trade waste systems

Open on NCC Online ↗

Delete clause C4D12 and insert TAS C4D12 as follows:

(1) A grease interceptor must contain a permanently fixed, ridged baffle constructed of a minimum 6 mm—

mild steel plate; or

other authorised material.

(2) A grease interceptor must be installed on a minimum of 75 mm compacted packing sand.

(3) A grease interceptor must have a minimum DN 50 vent where airtight covers are fitted.

(4) A grease interceptor installed underground must be constructed with—

minimum 100 mm concrete walls with a smooth internal finish; and

have suitable reinforcing mesh within the concrete.

(5) A grease interceptor installed above ground must—

be constructed of an authorised material; and

provide adequate structural support.

(6) The capacity of a grease interceptor must be authorised by the Permit Authority.

(7) A grease interceptor must be installed in a location that will facilitate ready access for maintenance and inspection.

Exemptions

Where the Permit Authority has not specified the capacity of a grease interceptor in accordance with C4D12(5), it must be—

equivalent to the maximum hourly discharge; and

no less than 250 litres below the outlet.