Tasmania variation · NCC 2025 Volume Three
TAS C4D14 Venting of grease traps
TAS Part C4 On-site liquid trade waste systems
Delete clause C4D14 and insert TAS C4D14 as follows:
(1) Grease trap chambers must provide adequate ventilation by providing—
two DN 100 vents in addition to the ventilation provided for the sanitary drainage system; or
appropriate mechanical ventilation.
(2) Anti-siphon vents must be—
a minimum of DN 50: and
connected to the outlet of the grease trap chamber.
Changed since NCC 2022. See NCC 2022 Volume Three TAS C4D14, or show what changed.
Delete clause C4D14 and insert TAS C4D14 as follows: (1) Grease trap chambers must provide adequate ventilation by providing … and connected to the outlet of the grease trap chamber.
Removed words are struck through; added words are highlighted. Comparison of the text only.