Tasmania variation · NCC 2025 Volume Three

TAS E3D3 Roofing of liquid trade waste generation areas

TAS Part E3 Stormwater - Roof drainage systems

Open on NCC Online ↗

Delete clause E3D3 and insert TAS E3D3 as follows:

(1) When a liquid trade waste generating process does not fully occur within a building, suitable roofing must prevent the entry of stormwater to the disposal system.

(2) When a liquid trade waste generating process occurs within a building where one or more sides are open to the weather, a vertical overhang of a minimum of 10° from the roofing must be provided.

(3) Where the wind driven rainwater is likely to enter under the roof in extreme storm conditions, the roof must overhang by a minimum of 10° from the roofing.

Changed since NCC 2022. See NCC 2022 Volume Three TAS E3D3, or show what changed.