TAS E3P1 Roof drainage systems
TAS Part E3 Stormwater - Roof drainage systems
Delete clause E3P1 and insert TAS E3P1 as follows:
(1) A roof drainage system must have the capacity to transfer the volume of water anticipated in a 5% annual exceedance probability rainfall event.
(2) Box and valley gutters must have capacity to transfer the volume of water anticipated in a 1% annual exceedance probability rainfall event.
(3) The annual exceedance probability must be appropriate to—
the importance of the building; and
the severity of potential damage to the property; and
The severity of loss of amenity, illness or injury that would result from the failure of the system.
Changed since NCC 2022. See NCC 2022 Volume Three TAS E3P1, or show what changed.
Delete clause E3P1 and insert TAS E3P1 as follows: (1) A roof drainage system must have the capacity to … injury that would result from the failure of the system.
Removed words are struck through; added words are highlighted. Comparison of the text only.