H1D7 Roof and wall cladding
Part H1 Structure · NCC 2019: 3.5, 3.51-3.5.5, 3.5.1-3.5.5
(1) Diagrams depicting relevant roofing and supporting members and associated terminology used to describe them are set out in Figure H1D7a and Figure H1D7b.
(2) Performance Requirement H1P1 is satisfied for sheet roofing if it complies with one or a combination of the following:
Metal roofing:
AS 1562.1; and
in wind regions B2, C and D in accordance with Figure 2.2.3 in Section 2 of the ABCB Housing Provisions (cyclonic areas), metal roof assemblies, their connections and immediate supporting members must be capable of remaining in position notwithstanding any permanent distortion, fracture or damage that might occur in the sheet or fastenings under the pressure sequences A to G defined in Table H1D7.
Plastic sheet roofing: AS 1562.3.
Metal sheet roofing: Part 7.2 of the ABCB Housing Provisions, provided the building is located in an area with a wind class of not more than N3.
(3) Performance Requirement H1P1 is satisfied for roof cladding if it complies with one or a combination of the following:
Terracotta, fibre-cement and timber slates and shingles: AS 4597.
For roof tiles—
AS 2050; or
Part 7.3 of the ABCB Housing Provisions, provided—
the building is located in an area with a wind class of not more than N3; and
the roof tiles comply with AS 2049; and
the roof has a pitch of not less than 15 degrees and not more than 35 degrees.
(4) Performance Requirement H1P1 is satisfied for timber and composite wall cladding if it is designed and constructed in accordance with—
for autoclaved aerated concrete wall cladding, AS 5146.1; or
for wall cladding, Part 7.5 of the ABCB Housing Provisions.
(5) Performance Requirement H1P1 is satisfied for a metal wall cladding if it is designed and constructed in accordance with AS 1562.1.
(6) Performance Requirement H1P1 is satisfied for external wall insulation and finish cladding systems, other than direct fix systems, if they are designed and constructed in accordance with AS 5346.
Table H1D7 Low-High-Low pressure sequence
Sequence
Number of cycles
Load
A
4500
0 to 0.45 Pt
B
600
0 to 0.6 Pt
C
80
0 to 0.8 Pt
D
1
0 to 1.0 Pt
E
80
0 to 0.8 Pt
F
600
0 to 0.6 Pt
G
4500
0 to 0.45 Pt
Table Notes
Pt is the ultimate limit state wind pressure on internal and external surfaces as determined in accordance with AS/NZS 1170.2, modified by an appropriate factor for variability, as determined in accordance with Table B1 of AS/NZS 1170.0.
The rate of load cycling must be less than 3 Hz.
The single load cycle (sequence D) must be held for a maximum of 10 seconds.
Figure H1D7a Section of a typical sheet roof
Figure H1D7b Section of a typical tile roof
Tables
Changed since NCC 2022. See NCC 2022 Volume Two H1D7, or show what changed.
(1) Diagrams depicting relevant roofing and supporting members and associated … set out in Figure H1D7a and Figure H1D7b. (2) Performance RequirementH1P1 Requirement H1P1 is satisfied for sheet roofing if it complies with one or a combination of the following: Metal roofing: AS 1562.1; and in wind regions B2, C and D in accordance with Figure 2.2.3 in Section … a wind class of not more than N3. (3) Performance RequirementH1P1 Requirement H1P1 is satisfied for roof cladding if it complies with one … 15 degrees and not more than 35 degrees. (4) Performance RequirementH1P1 Requirement H1P1 is satisfied for timber and composite wall cladding if it … cladding, Part 7.5 of the ABCB Housing Provisions. (5) Performance RequirementH1P1 Requirement H1P1 is satisfied for a metal wall cladding if it is designed and constructed in accordance with AS 1562.1. (6) Performance Requirement H1P1 is satisfied for external wall insulation and finish cladding systems, other than direct fix systems, if they are designed and constructed in accordance with AS 5346. Table H1D7 Low-High-Low pressure sequence Sequence Number of cycles Load … sheet roof Figure H1D7b Section of a typical tile roof
Removed words are struck through; added words are highlighted. Comparison of the text only.