Queensland variation · NCC 2025 Volume Two

QLD H1P3 Termite management measures

QLD Part H1 Structure

Open on NCC Online ↗

Insert QLD clause H1P3 in clause H1P3 as follows:

(1) The risk of primary building element in a Class 1 or 10 building being damaged by subterranean termites must be adequately minimised by the use of a suitable termite management measure that—

if it serves a non-temporary Class 1 building, has a design life of at least 50 years; or

if it serves a building not specified in (a), has a design life of at least 50 years or the specified design life of the building, whichever is the lesser; or

is easily and readily accessible for replenishment or replacement and is capable of being replenished or replaced.

(2) A termite management measure required by (1), to the degree necessary, must—

be accessible to enable the installation, maintenance and inspection of the termite management measure to be carried out; and

incorporate suitable measures to adequately minimise the risk of the termite management measure inadvertently being damaged, bridged or breached.

Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two QLD H1P3.