Specification clause · NCC 2025 Volume Two

S42C2 Heating and cooling loads

Specification 42 House energy rating software · NCC 2019: 3.12.0.1

Open S42C2 on NCC Online ↗

(1) A building must achieve an energy rating, including the separate heating and cooling load limits, using house energy rating software, of greater than or equal to—

7 stars; or

for a building in climate zones 1 or 2, 6.5 stars if the building has an outdoor living area as described in (3) which is fully covered with an impervious roof having a Total R-Value greater than or equal to 1.5 (for downward heat flow); or

for a building in climate zones 1 or 2, 6 stars if the building has an outdoor living area as described in (3) which—

is fully covered with an impervious roof having a Total R-Value greater than or equal to 1.5 (for downward heat flow); and

has at least one permanently installed ceiling fan.

(2) The heating and cooling load limits in (1) are specified in the ABCB Standard for NatHERS Heating and Cooling Load Limits.

(3) An outdoor living area in (1)(b) and (1)(c) is a space that—

is directly adjoining, and directly accessible from, a general purpose living area of a Class 1 building such as a lounge, kitchen, dining or family room, which is not a room for sleeping or specialist tasks such as a study or home theatre; and

has a floor area greater than or equal to 12.0 m2; and

has length and width dimensions greater than or equal to 2.5 m each; and

has an opening height above floor level greater than or equal to 2.1 m; and

has one side permanently open with a second side either—

permanently open; or

readily openable.

(4) The sides referred to in (3)(e) must be greater than or equal to 900 mm from an allotment boundary or 900 mm from an obstruction to the breeze path such as a building, fence or other structure.

(5) Where a ceiling fan is required as part of compliance with (1)(c), the fan must—

be permanently installed; and

have a speed controller; and

serve the whole room, with the floor area that a single fan serves not exceeding—

15 m2 if it has a blade rotation diameter of less than 1200 mm; and

25 m2 if it has a blade rotation diameter of greater than or equal to 1200 mm.

Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two S42C2.

Defined terms used