Table S1C2c FRLs deemed to be achieved by walls — gypsum
Specification 1 Fire-resistance of building elements
| Gypsum type | Minimum thickness (mm) of principal material for FRLs | ||||
|---|---|---|---|---|---|
| 60/60/60 | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 | |
| Solid gypsum blocks | 75 | 90 | 100 | 110 | 125 |
| Gypsum — perlite or gypsum vermiculite-plaster on metal lath and channel (non-load bearing walls only) | 50 | 50 | 65 | - | - |
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table for S1C2 Rating
Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two Table S1C2c.