Governing requirement · NCC 2025 Volume One

A6G1 Determining a building classification

Part A6 Building classification · NCC 2019: A6.0

Open A6G1 on NCC Online ↗

(1) The classification of a building or part of a building is determined by the purpose for which it is designed, constructed or adapted to be used.

(2) Each part of a building must be classified according to its purpose and comply with all the appropriate requirements for its classification.

(3) A room that contains a mechanical, thermal or electrical facility or the like that serves the building must have the same classification as the major part or principal use of the building or fire compartment in which it is situated.

(4) Unless another classification is more suitable, an occupiable outdoor area must have the same classification as the part of the building to which it is associated.

Exemptions

For A6G1(1) where a part of a building has been designed, constructed or adapted for a different purpose and is less than 10% of the floor area of the storey it is situated on, the classification of the other part of the storey may apply to the whole storey.

A6G1(3) does not apply to an electricity network substation.

Limitations

Exemption (1) does not apply where the minor use of a building is a laboratory, a Class 9b early childhood centre, or a Class 2, 3 or 4 part of a building.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One A6G1.

Defined terms used