Deemed-to-Satisfy Provision · NCC 2025 Volume One

E2D7 Buildings more than 25 m in effective height: Class 9a buildings

Part E2 Smoke hazard management · NCC 2019: Table E2.2a

Open E2D7 on NCC Online ↗

(1) A Class 9a building must be provided with—

an automatic smoke detection and alarm system complying with Specification 20; and

a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1,

if the building is more than 25 m in effective height.

(2) For the purposes of (1), ‘vertically separated fire compartments ’ are fire compartments above and below each other, and not fire compartments within the same storey.

Notes

A building more than 25 m in effective height requires a sprinkler system under E1D4.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One E2D7.
Can't meet E2D7? A Performance Solution must meet the Performance Requirements it satisfies: E2P1, E2P2. Start a Performance Solution →

Clauses referred to

Defined terms used