Verification Method · NCC 2025 Volume One

E3V2 Emergency alerts on the use of lifts

Part E3 Lift installations · NCC 2019: EV3.2

Open E3V2 on NCC Online ↗

(1) Compliance with E3P3 is verified when building occupants are provided with automatic warning that lifts must not be used during a fire emergency.

(2) The automatic warning must—

be initiated by a smoke hazard management system complying with Part E2; and

be provided via a sound system complying with the relevant provisions of AS 1670.4; and

have a flashing warning sign installed in accordance with AS 1670.4 displaying the words “do not use lift”.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One E3V2.