Verification Method · NCC 2025 Volume One
E3V2 Emergency alerts on the use of lifts
Part E3 Lift installations · NCC 2019: EV3.2
(1) Compliance with E3P3 is verified when building occupants are provided with automatic warning that lifts must not be used during a fire emergency.
(2) The automatic warning must—
be initiated by a smoke hazard management system complying with Part E2; and
be provided via a sound system complying with the relevant provisions of AS 1670.4; and
have a flashing warning sign installed in accordance with AS 1670.4 displaying the words “do not use lift”.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One E3V2.