Verification Method · NCC 2025 Volume One

F2V1 Overflow protection

Part F2 Wet areas and overflow protection · NCC 2019: FV1.2

Open F2V1 on NCC Online ↗

Compliance with F2P1 is verified when the flow rate of the in-built overflow for all vessels in the room is greater than the flow rate of the source filling the vessel.

Applications

F2V1 only applies to bathrooms, laundries and the like in a Class 2 or 3 building or a Class 4 part of a building.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One F2V1.