Performance Requirement · NCC 2025 Volume One

F7P1 Sound transmission through floors

Part F7 Sound transmission and insulation · NCC 2019: NT FP5.1, FP5.1

Open F7P1 on NCC Online ↗
Varied in NT. Check the variation for your state.

A floor separating sole-occupancy units or a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby, or the like, or parts of a different classification, must minimise the transmission of airborne and impact generated sound such that the separating floor, including the effect of services and their penetrations, has—

a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45 for airborne sound; and

a weighted standardised impact sound pressure level (LnT,w) not more than 62 for impact generated sound.

Applications

F7P1 only applies to a Class 2 or 3 building.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One F7P1.