Specification clause · NCC 2025 Volume One
S19C13 Lighting for a fire control room
Specification 19 Fire control centres · NCC 2019: Spec E1.8: 12
Emergency lighting in accordance with the Deemed-to-Satisfy Provisions of Part E4 must be provided in a fire control room, except that an illumination level of not less than 400 lux must be maintained at the surface of the plan table.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S19C13.