Specification clause · NCC 2025 Volume One

S1C3 FRLs determined by calculation

Specification 1 Fire-resistance of building elements · NCC 2019: Sch. 5: 3

Open S1C3 on NCC Online ↗

If the FRL of a building element is determined by calculation based on a tested prototype—

the building element may vary from the prototype in relation to—

length and height if it is a wall; and

height if it is a column; and

span if it is a floor, roof or beam; and

conditions of support; and

to a minor degree, cross-section and components; and

the report must demonstrate by calculation that the building element would achieve the FRL if it is subjected to the regime of the Standard Fire Test in relation to—

structural adequacy (including deflection); and

integrity; and

insulation; and

the calculations must take into account—

the temperature reached by the components of the prototype and their effects on strength and modulus of elasticity; and

appropriate features of the building element such as support, restraint, cross-sectional shape, length, height, span, slenderness ratio, reinforcement, ratio of surface area to mass per unit length, and fire protection; and

features of the prototype that influenced its performance in the Standard Fire Test although these features may not have been taken into account in the design for dead and live load; and

features of the conditions of test, the manner of support and the position of the prototype during the test, that might not be reproduced in the building element if it is exposed to fire; and

the design load of the building element in comparison with the tested prototype.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S1C3.