Specification clause · NCC 2025 Volume One

S2C21 Filling of column spaces

Specification 2 Descriptions of elements referred to in Specification 1 · NCC 2019: Sch. 5 (Annex): 9

Open S2C21 on NCC Online ↗

(1) The spaces between the fire-protective material and the steel (and any re-entrant parts of the column itself) must be filled solid with a fire-protective material like concrete, gypsum or grout.

(2) The insides of hollow sections, including pipes, need not be filled.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S2C21.