Specification clause · NCC 2025 Volume One

S30C4 Protection from heat

Specification 30 Installation of boilers and pressure vessels · NCC 2019: Spec G2.2: 2.3

Open S30C4 on NCC Online ↗

Building elements surrounding a boiler must be protected from any surface heat by refractory material or effective air spaces so that—

steel elements do not exceed a temperature of more than 300°C; and

concrete elements do not exceed a temperature of more than 200°C; and

timber elements do not exceed a temperature of more than 150°C.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S30C4.