Specification clause · NCC 2025 Volume One

S34C4 Services — proposed and reference building

Specification 34 Modelling parameters for J1V3 · NCC 2019: Spec JVb: 4

Open S34C4 on NCC Online ↗

For the modelling of services for the purposes of calculating annual greenhouse gas emissions —

system demand and response for all items of plant must be calculated on a not less frequent than hourly basis; and

energy usage of all items of plant must be calculated with allowances for—

part load performance; and

staging to meet system demand; and

energy usage of cooling plant must be calculated with allowances for—

the impact of chilled water temperature on chiller efficiency; and

the impact of condenser water temperature on water-cooled plant efficiency; and

the impact of ambient temperature on air-cooled plant efficiency; and

the energy use of primary pumps serving individual chillers; and

the energy use of auxiliary equipment, including controls and oil heating for chillers; and

thermal losses in the chilled water system; and

the impact of chilled water temperature on thermal losses in the chilled water system; and

energy usage of water heating systems for space heating must be calculated with allowances for—

the impact of water temperature on water heater efficiency; and

the energy use of primary or feedwater pumps serving individual water heaters; and

thermal losses in water heating systems; and

the thermal mass of water heating systems, accounting for thermal losses during periods when the system is not operating; and

energy usage of fan and pump systems must be calculated with allowances for—

the method of capacity regulation; and

the use of either fixed or variable pressure control; and

energy usage of pump systems must be calculated with allowances for the system fixed static pressure head; and

energy usage of auxiliary equipment associated with co-generation and tri-generation systems, including pumps, cooling towers and jacket heaters, must be calculated; and

if energy usage for each is the same in the proposed building and the reference building, omission from the calculation for both the proposed building and reference building may be made for—

heated water supply for food preparation and sanitary purposes; and

lifts; and

escalators; and

electric vehicle charging; and

energy use of a lift in a building with more than one classification may be apportioned according to the number of storeys of the part for which the annual greenhouse gas emissions are being calculated.

Changed since NCC 2022. See NCC 2022 Volume One S34C4, or show what changed.

For the modelling of services for the purposes of calculating … pumps, cooling towers and jacket heaters, must be calculated; and where the if energy usage of the heated water supply for food preparation and sanitary purposes or the energy usage of lifts and escalators each is the same in the proposed building and the reference building, they may be omitted omission from the calculation of for both the proposed building and the reference building; building may be made for — heated water supply for food preparation and sanitary purposes; and lifts; and escalators; and electric vehicle charging; and energy use of a lift in a building with … of the part for which the annual greenhouse gas emissions and thermal comfort level are being calculated.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Defined terms used