Specification clause · NCC 2025 Volume One

S44C3 Cooling load limit

Specification 44 Calculation of heating load limit, cooling load limit and thermal energy load limit

Open S44C3 on NCC Online ↗

(1) The cooling load limit of a space, measured in MJ/m2.annum, is calculated in accordance with the following formula:

[formula] (2) In the formula at (1)—

[formula] = the cooling load limit (MJ/m2.annum); and

[formula] = the total annual cooling degree hours of the building location; and

[formula] = the total annual dehumidification gram hours of the building location; and

[formula] = the area adjustment factor for the cooling load limit, determined in accordance with Table S44C3.

Table S44C3 Area adjustment factors for the cooling load limit

Total area of the habitable rooms (AH)

Area adjustment factor (FC)

≤ 50 m2

1.34

> 50 m2 and ≤ 200 m2

[formula] | > 200 m2 and ≤ 1000 m2

[formula] | > 1000 m2

0.71

Tables

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S44C3.