S46C2 Determination of peak efficiency and fan power ratio
Specification 46 Determination of peak efficiency and fan power ratio
(1) The efficiency of a selected fan is the product of its impeller efficiency (including any casing), motor efficiency and the integrated motor control equipment multiplier in (2).
(2) The value of the integrated motor control equipment multiplier—
where the fan motor is not capable of variable speed operation or has an external variable speed control device, is 1; or
where the fan motor has integrated variable speed control capability and the motor input power at peak efficiency point is less than 5 kW, [formula] , where—
[formula] = the motor input power of the fan (kW) at peak efficiency point; and
[formula] = natural logarithm; or
where the fan motor has integrated variable speed control capability and the motor input power at peak efficiency point is greater than or equal to 5 KW, is 1.04.
(3) The fan power ratio of an individual fan must be calculated in accordance with the following formula:
[formula] where—
[formula] = the fan power ratio of the fan; and
[formula] = the efficiency calculated using the equation at J6D5(2) or J6D5(3) as applicable, with electrical input power [formula] , as determined at (5); and
[formula] = the static efficiency of the selected fan at the duty point for installation type A or C, or the total efficiency at the duty point for installation type B or D.
(4) The average fan power ratio of multiple fans must be calculated in accordance with the following formula:
[formula] where—
[formula] = the average fan power ratio of multiple fans; and
[formula] = the electrical input power of each selected fan at duty point, calculated in accordance with (5); and
[formula] = the electrical input power of each reference fan at duty point, calculated in accordance with (6).
(5)
[formula] must be calculated in accordance with the following:
[formula] where—
[formula] = the static pressure (Pa) at the duty point for installation type A or C or the total pressure (Pa) at the duty point for installation type B or D; and
[formula] = the flow (m3/s) at the duty point; and
[formula] = the static efficiency at the duty point for installation type A or C or the total efficiency at the duty point for installation type B or D.
(6)
[formula] must be calculated in accordance with the following formula:
[formula] where—
[formula] = the static pressure (Pa) at the duty point for installation type A or C or total pressure (Pa) at the duty point for installation type B or D; and
[formula] = the flow (m3/s) at the duty point; and
[formula] = the efficiency calculated using the equation at J6D5(2) or (3) as applicable with electrical input power [formula] .