Specification clause · NCC 2025 Volume One

S8C4 Additional requirements for vertically spanning external wall panels adjacent to columns

Specification 8 Performance of external walls in fire · NCC 2019: Spec C1.11: 4

Open S8C4 on NCC Online ↗

(1) Where vertically spanning external wall panels are located adjacent to columns, connections to the panels must be located and/or detailed to minimise forces that may develop between the panels and columns arising from the restraint of differential displacement.

(2) The requirements of (1) are satisfied by—

detailing the connections and/or the supporting member to sustain a relative outward displacement of (d) between the panels and columns at the connection height where d(m) is calculated as—

the square of the connection height (m) divided by one hundred and twenty-five, when the connection height is less than 5 m; or

the connection height (m) divided by twenty-five, when the connection height (m) is greater than or equal to 5 m; or

in situations where an eaves tie member is used to provide lateral support to external wall panels, the tie member is connected to the panels no closer than a distance (s) from the column where s(m) is taken as one quarter of the panel height (m).

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S8C4.