Table F8D5 Roof space ventilation requirements

Part F8 Condensation management

Open Table F8D5 on NCC Online ↗
Roof pitchVentilation openings
<10°20,000 mm2/m provided at eaves or low level, or at each of two opposing ends for gable roofs
≥10° and <75°7,000 mm2/m provided at the eaves or low level and 5,000 mm2/m provided at high level or ridge

For roofs less than 10 m2, 7,000 mm2/m provided at eaves or low level roof perimeter and 5,000 mm2/m provided at ridge or high level for skillion roofs

20,000 mm2/m provided at the eaves or low level and 5,000 mm2/m provided at ridge or high level for skillion roofs

Table Notes

Ventilation openings are specified as a minimum free open area per metre length. The longest total plan dimension is based on the roof length irrespective of the number of storeys beneath.

Total low level ventilation openings are calculated based on twice the longest total plan dimension of the roof, except for mono pitch or skillion roofs that are calculated based on the longest total plan dimension of the roof. Total high level ventilation is calculated based on the longest total plan dimension of the roof.

High level openings are openings provided at the ridge or not more than 900 mm below the ridge or highest point of the roof space, measured vertically or 1/3 of the height of the roof below highest point of the roof, whichever is least.

Table for F8D5 Ventilation of a roof space with the primary insulation layer not parallel to the roof plane

Changed since NCC 2022. See NCC 2022 Volume One Table F8D5, or show what changed.

Roof pitch | Ventilation openings <10° | 25,000 20,000 mm2/m provided at eaves or low level, or at each of two opposing ends ≥10° for gable roofs For roofs less than 10 m2, 7,000 mm2/m provided at eaves or low level roof perimeter and <15° | 25,000 5,000 mm2/m provided at ridge or high level for skillion roofs 20,000 mm2/m provided at the eaves or low level and 5,000 mm2/m provided at ridge or high level ≥15° for skillion roofs ≥10° and <75° | 7,000 mm2/m provided at the eaves or low level and 5,000 mm2/m provided at high level, plus an additional 18,000 mm2/m at the eaves if the roof has a cathedral ceiling level or ridge Table Notes Ventilation openings are specified as a minimum free open area per metre length. The longest total plan dimension is based on the roof length irrespective of the number of storeys beneath. Total low level ventilation openings are calculated based on twice the longest horizontal total plan dimension of the roof, except for mono pitch or skillion roofs that are calculated based on the longest total plan dimension of the roof. For Total high level ventilation is calculated based on the purposes longest total plan dimension of this table, high the roof. High level openings are openings provided at the ridge or not … the ridge or highest point of the roof space, measured vertically. vertically or 1/3 of the height of the roof below highest point of the roof, whichever is least.

Removed words are struck through; added words are highlighted. Comparison of the text only.