Table · NCC 2025 Volume One

Table J6D11c Minimum climate specific part load value for a connected group of air-cooled chiller plant

Part J6 Air-conditioning and ventilation

Open Table J6D11c on NCC Online ↗
Climate zoneDesign load not greater than 900 kWDesign load greater than 900 kW
14.13.9
24.84.5
34.34.1
44.94.5
55.14.8
65.45.0
75.24.9
85.65.5