Table · NCC 2025 Volume One
Table J6D11c Minimum climate specific part load value for a connected group of air-cooled chiller plant
Part J6 Air-conditioning and ventilation
| Climate zone | Design load not greater than 900 kW | Design load greater than 900 kW |
|---|---|---|
| 1 | 4.1 | 3.9 |
| 2 | 4.8 | 4.5 |
| 3 | 4.3 | 4.1 |
| 4 | 4.9 | 4.5 |
| 5 | 5.1 | 4.8 |
| 6 | 5.4 | 5.0 |
| 7 | 5.2 | 4.9 |
| 8 | 5.6 | 5.5 |
Table for J6D11 Refrigerant chillers
New in NCC 2025. No Table J6D11c in NCC 2022 Volume One; it may have moved or been renumbered.