Table · NCC 2025 Volume One
Table S1C2l FRLs deemed to be achieved by hot-rolled steel beams (including an open-web joist, girder, truss, etc.) exposed on no more than 3 sides
Specification 1 Fire-resistance of building elements
| Fire protection | Minimum thickness (mm) of principal material for FRLs | ||||
|---|---|---|---|---|---|
| 60/–/– | 90/–/– | 120/–/– | 180/–/– | 240/–/– | |
| Concrete — cast in-situ | 25 | 30 | 40 | 50 | 65 |
| Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour | 20 | 25 | 35 | 50 | 55 |
| Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath | 20 | 20 | 25 | 35 | 45 |
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table for S1C2 Rating
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S1C2l.