Table S1C2l FRLs deemed to be achieved by hot-rolled steel beams (including an open-web joist, girder, truss, etc.) exposed on no more than 3 sides

Specification 1 Fire-resistance of building elements

Open Table S1C2l on NCC Online ↗
Fire protectionMinimum thickness (mm) of principal material for FRLs
60/–/–90/–/–120/–/–180/–/–240/–/–
Concrete — cast in-situ2530405065
Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour2025355055
Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath2020253545

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table for S1C2 Rating

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S1C2l.