Table · NCC 2025 Volume One
Table S2C26a Reinforcement of gypsum-perlite or gypsum-vermiculite plaster sprayed to contour — vertical members with H or I cross-section
Specification 2 Descriptions of elements referred to in Specification 1
| Surface to be protected | Reinforcement required if smaller dimension of surface exceeds (mm) | Max spacing of fixings of the mesh to surface (mm) |
|---|---|---|
| Vertical | 450 | 450 |
| Non-vertical | 300 | 300 |
| Underside | 300 | 300 |
| Upper side of a horizontal surface | Not required | N/A |
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S2C26a.