Table · NCC 2025 Volume One

Table S7C7 Other materials

Specification 7 Fire hazard properties

Open Table S7C7 on NCC Online ↗
Material or assembly locationFlammability IndexSpread-of-Flame IndexSmoke-Developed Index
Fire control rooms subject to Specification 19 and fire-isolated exits, other than a sarking-type material used in a ceiling or used as an attachment or part of an attachment to a building element. Note 1N/A02
Class 9b buildings used as a theatre, public hall or the like: Any part of fixed seating in the audience area or auditorium.N/A05
Class 9b buildings used as a theatre, public hall or the like: A proscenium curtain required by Specification 32.N/A03
Escalators, moving walkways or non-required non fire-isolated stairway or pedestrian ramps subject to Specification 14.N/A05
Sarking-type materials: In a fire control room subject to Specification 19 or a fire-isolated exit or fire control room used in the form of an exposed wall or ceiling.0N/AN/A
Sarking-type materials: In other locations. Note 25N/AN/A
Other materials or locations and insulation materials other than sarking-type material. Notes 2 and 3N/A98 if the Spread-of-Flame Index is more than 5

Table Notes

In a fire control room or fire-isolated stairway, a material used as an attachment or part of an attachment to a building element must, if combustible, be attached directly to a non-combustible substrate and not exceed 1 mm finished thickness.

A material, other than one located within a fire-isolated exit or fire control room, may be covered on all faces by concrete or masonry not less than 50 mm thick, as an alternative to meeting the specified indices.

In the case of a composite member or assembly, the member or assembly must be constructed so that when assembled as proposed in a building—

any material which does not comply with this table is protected on all sides and edges from exposure to the air; and

the member or assembly, when tested in accordance with Specification 3, has Spread-of-Flame Index and Smoke-Developed Index not exceeding those prescribed in this table; and

the member or assembly retains the protection in position so that it prevents ignition of the material and continues to screen it from access to free air for a period of not less than 10 minutes.

Table for S7C7 Other materials

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S7C7.