Housing Provisions clause · ABCB Housing Provisions 2022

10.2.18 Unenclosed showers

Part 10.2 Wet area waterproofing

Open 10.2.18 on NCC Online ↗

(1) Unenclosed showers must be constructed as follows:

A waterstop must be installed a minimum horizontal distance of 1500 mm from the shower rose.

The vertical leg of the waterstop must finish—

flush with the top surface of the floor (see Figure 10.2.18); and

where the waterstop intersects with a wall or is joined—

the junction must be waterproof; or

the whole wet area floor must be waterproofed and drained to a floor waste as for the shower area.

(2) In the case of (1)(b)(ii)(B), at doorways, where the height of the tiling angle needs to be adjusted for tiling purposes, the angle must be fixed with a sealant compatible with the waterproofing membrane without damaging the waterproofing system.

Figure 10.2.18 Typical termination of membrane at extent of shower area

Figure Notes

Fall is to be provided in accordance with 10.2.12.

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 10.2.18.