10.7.1 Sound insulation requirements
Part 10.7 Sound insulation · NCC 2019: 3.8.6.2, NT 3.8.6.2
Varied in NT. Check the variation for your state.
(1) A separating wall between Class 1 buildings, or a wall that separates a Class 1 building from a Class 10a building which is not associated with the Class 1 building must—
have an Rw + Ctr (airborne) not less than 50; and
be of discontinuous construction if it separates a bathroom, sanitary compartment, laundry or kitchen in one Class 1 building from a habitable room (other than a kitchen) in an adjoining Class 1 building (see Figure 10.7.1).
(2) A wall required to have sound insulation must continue to—
the underside of the roof above; or
a ceiling that provides the sound insulation required for the wall.
Figure 10.7.1 Required airborne and impact sound insulation — Plan view
Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 10.7.1.