Housing Provisions clause · ABCB Housing Provisions 2025

10.7.1 Sound insulation requirements

Part 10.7 Sound insulation · NCC 2019: 3.8.6.2, NT 3.8.6.2

Open 10.7.1 on NCC Online ↗
Varied in NT. Check the variation for your state.

(1) A separating wall between Class 1 buildings, or a wall that separates a Class 1 building from a Class 10a building which is not associated with the Class 1 building must—

have an Rw + Ctr (airborne) not less than 50; and

be of discontinuous construction if it separates a bathroom, sanitary compartment, laundry or kitchen in one Class 1 building from a habitable room (other than a kitchen) in an adjoining Class 1 building (see Figure 10.7.1).

(2) A wall required to have sound insulation must continue to—

the underside of the roof above; or

a ceiling that provides the sound insulation required for the wall.

Figure 10.7.1 Required airborne and impact sound insulation — Plan view

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 10.7.1.