13.5.2 Ceiling fans
Part 13.5 Ceiling fans · NCC 2019: 3.12.4.3
Varied in NT. Check the variation for your state.
Ceiling fans must be installed in accordance with Table 13.5.2 in—
climate zones 1, 2 and 3; and
climate zone 5 in New South Wales and Queensland.
Table 13.5.2 Minimum ceiling fan requirements in climate zones 1, 2, 3 and 5
Size of room (m²)
Minimum number and diameter (mm) of ceiling fans required in a bedroom in climate zones 1, 2 and 3
Minimum number and diameter (mm) of ceiling fans required in a habitable room other than a bedroom in climate zones 1, 2, 3 and 5 (NSW and Qld)
<15
1 x 900
1 x 900
≥15<20
1 x 1200
1 x 1200
≥20<25
1 x 1200
1 x 1400
≥25<30
1 x 1400
2 x 1200
≥30<45
1 x 1400
2 x 1400
≥45<50
2 x 1400
3 x 1200
≥50
2 x 1400
3 x 1400