Northern Territory variation · ABCB Housing Provisions 2022

NT 13.5.2 Air movement

NT Part 13.5 Ceiling fans · varies 13.5.2 Ceiling fans

Open on NCC Online ↗

(1) Air movement must be provided to habitable rooms in accordance with Table NT 13.5.2.

(2) Air movement required by (1) may be provided through an opening from an adjoining room (including an enclosed verandah) if—

the adjoining room is not a sanitary compartment; and

the opening between the adjoining room and the habitable room complies with Table NT 13.5.2 as if it were a ventilation opening to the habitable room or a proportion there of if some ventilation is provided from another source; and

the ventilation opening to the adjoining room complies with Table NT 13.5.2 for the total area of the floor of the adjoining room and the proportion of the habitable room that is ventilated from the adjoining room.

Insert NT table (13.5.2) 13.5.2 as follows:

NT Table 13.5.2: Minimum total ventilation opening area as a percentage of the floor area for each habitable room

Climate zone

Minimum total ventilation opening area per habitable room (percentage of the area of the floor of the habitable room)

Without a ceiling fan or evaporative cooler

With a ceiling fan

With an evaporative cooler

1

15%

12.5%

15%

3

12.5%

7.5%

7.5%

Changed in NCC 2025. See ABCB Housing Provisions 2025 NT 13.5.2, or show what changed.

Insert NT clause 13.5.2 in clause 13.5.2 as follows: (1) Air movement must be provided to habitable rooms in … evaporative cooler 1 15% 12.5% 15% 3 12.5% 7.5% 7.5%

Removed words are struck through; added words are highlighted. Comparison of the text only.

The national clause