4.2.15 Strip footings Class A, S and M sites
Part 4.2 Footings, slabs and associated elements
Strip footings for Class A, S and M sites must comply with—
for Class A and S sites — Tables 4.2.15a, 4.2.15b and Figure 4.2.15a; and
for Class M sites — Table 4.2.15c and Figure 4.2.15b.
Table 4.2.15a Dimensions and reinforcement for strip footing systems for Class A sites
Type of construction
D (mm)
B (mm)
Reinforcement (top and bottom)
Clad frame
300
300
3–L8TM
Articulated masonry veneer
300
300
3–L8TM
Masonry veneer
300
300
3–L8TM
Articulated full masonry
300
400
4–L8TM
Full masonry
300
400
4–L8TM
Table Notes
All masonry walls must be supported on strip footings.
Internal strip footings must be of the same proportions as the external footings and run from external footing to external footing. ‘Side slip joints’ consisting of a double layer of polyethylene must be provided at the sides of the footing only.
Infill floors may be concrete slabs, brick paving, stone flags or compacted and stabilised earth. For concrete slab infill panels, mesh may be required to control shrinkage in slab panels and around openings or restrained regions. Concrete infill slabs must use a minimum of SL62 mesh to control shrinkage (see also 4.2.19).
Where footings are wider than the specified width, an extra bottom bar or equivalent of the same bar size is required for each 100 mm additional width. If strip footings deeper than those required are used, the reinforcement must be increased to match that specified for the deepened proportions.
The measurement of Df is greater or equal to D plus 75 mm.
Alternative reinforcing sizes must comply with AS 2870.
Table 4.2.15b Dimensions and reinforcement for strip footing systems for Class S sites
Type of construction
D (mm)
B (mm)
Reinforcement (top and bottom)
Clad frame
400
300
3–L8TM
Articulated masonry veneer
400
300
3–L8TM
Masonry veneer
400
300
3–L8TM
Articulated full masonry
400
400
4–L11TM
Full masonry
500
400
4–L11TM
Table Notes
All masonry walls must be supported on strip footings.
Internal strip footings must be of the same proportions as the external footings and run from external footing to external footing. ‘Side slip joints’ consisting of a double layer of polyethylene must be provided at the sides of the footing only.
Infill floors may be concrete slabs, brick paving, stone flags or compacted and stabilised earth. For concrete slab infill panels, mesh may be required to control shrinkage in slab panels and around openings or restrained regions. Concrete infill slabs must use a minimum of SL62 mesh to control shrinkage (see also 4.2.19).
Where footings are wider than the specified width, an extra bottom bar or equivalent of the same bar size is required for each 100 mm additional width. If strip footings deeper than those required are used, the reinforcement must be increased to match that specified for the deepened proportions.
The measurement of Df is greater or equal to D plus 75 mm.
Alternative reinforcing sizes must comply with AS 2870.
Table 4.2.15c Dimensions and reinforcement for strip footing systems for Class M sites
Type of construction
D (mm)
B (mm)
Reinforcement (top and bottom)
Clad frame
400
300
3-L11TM
Articulated masonry veneer
450
300
3-L11TM
Masonry veneer
500
300
3-L12TM
Articulated full masonry
600
400
4-L12TM
Full masonry
900 Note 2
400
4-L12TM
Table Notes
All masonry walls must be supported on strip footings.
For beams 700 mm or deeper, as specified in the table above, internal footings must be provided at no more than 6 m centres and at re-entrant corners to continue footings to the opposite external footing. Internal strip footings must be of the same proportions as the external footings and run from external footing to external footing. ‘Side slip joints’ consisting of a double layer of polyethylene must be provided at the sides of the footing only.
Infill floors must only be used for Class A and S sites.
Where footings are wider than the specified width, an extra bottom bar or equivalent of the same bar size is required for each 100 mm additional width. If strip footings deeper than those required are used, the reinforcement must be increased to match that specified for the deepened proportions.
The measurement of Df is greater or equal to D plus 75 mm.
Alternative reinforcing sizes must comply with AS 2870.
For Class M articulated full masonry and full masonry, internal strip footings must be of the same proportions as the external footing and run from external footing to external footing.
Figure 4.2.15a Strip footing systems for Class A and S sites
Figure Notes
See Notes to Tables 4.2.15a and 4.2.15b.
Figure 4.2.15b Strip footing system for Class M sites
Figure Notes
See Notes Tables 4.2.15a, 4.2.15b and 4.2.15c.
Tables
- Table 4.2.15a Dimensions and reinforcement for strip footing systems for Class A sites
- Table 4.2.15b Dimensions and reinforcement for strip footing systems for Class S sites
- Table 4.2.15c Dimensions and reinforcement for strip footing systems for Class M sites