Part 4.2 Footings, slabs and associated elements
46 clauses · Open on NCC Online ↗
- 4.2.1 ApplicationPart 4.2 is subject to the limitations set out in H1D4(2).
- 4.2.2 Site classificationThe foundations where footings and slabs are to be located must be classified in accordance with AS 2870.
- 4.2.3 Excavation for footings NSWExcavation for footings, including thickenings for slabs and pads must be clean cut with vertical sides, wherever possible. (2) The base of the…
- 4.2.4 Filling under concrete slabsFilling placed under a slab (except where the slab is suspended) must comply with the following: Filling must be either controlled fill or rolled…
- 4.2.5 Foundations for footings and slabsFootings and slabs, including internal and edge beams, must be founded on soil with an allowable bearing pressure as follows: Slab panels, load…
- 4.2.6 Slab edge support on sloping sitesFootings and slabs installed on the low side of sloping sites must be as follows: Slab panels — in accordance with 4.2.5(a). Edge beams— supported…
- 4.2.7 Stepped footingsStepped strip footings must— have a base that is horizontal or be sloped at not more than 1:10; or be stepped in accordance with one of the methods…
- 4.2.8 Vapour barriers NSW SAA vapour barrier must be installed under slab-on-ground construction for a Class 1 building and for a Class 10 building where the slab is continuous…
- 4.2.9 Edge rebatesEdge rebates for slab-on-ground and stiffened raft with masonry cavity or veneer construction must comply with the following: The rebate must not be…
- 4.2.10 Concrete SAConcrete must comply with the following: Concrete must comply with AS 3600; and— have a strength at 28 days of not less than 20 MPa (denoted as N20…
- Table 4.2.11a Alternative mesh/reinforcing bar sizesTrench mesh (TM) | Area — mm2 | Reinforcing bar alternative | Trench mesh alternative 2-L8TM | 91 | 2-N10 or 1-N12 | Not applicable 3-L8TM | 136 |…
- Table 4.2.11b Minimum lap for reinforcementReinforcement | Minimum splice | Minimum lap at “T” intersections | Minimum lap at “L” intersections Steel reinforcing bars ≤12 mm diameter | 500 mm…
- 4.2.11 Steel reinforcementMaterials used for reinforcing steel must comply with AS 2870 and be— welded wire reinforcing fabric; or trench mesh; or steel reinforcing bars. (2)…
- 4.2.12 Footing and slab constructionFooting and slab construction, including size and placement of reinforcement, must be in accordance with the relevant provisions of— 4.2.13 for…
- Table 4.2.13a Stumps supporting single storey timber floor and metal roofFloor load area (m2) | Dimension (mm) | Roof load area (m2) 0 | 6 | 12 3 | Square pad footing size | 250 x 250 | 300 x 300 | 350 x 350 8 | Square…
- Table 4.2.13b Stumps supporting single storey tiled floor and tiled roofFloor load area (m2) | Dimension (mm) | Roof load area (m2) 0 | 6 | 12 3 | Square pad footing size | 300 x 300 | 400 x 400 | 450 x 450 8 | Square…
- Table 4.2.13c Stumps supporting double storey timber floor and metal roofFloor load area (m2) | Dimension (mm) | Roof load area (m2) 0 | 6 | 12 3 | Square pad footing size | 350 x 350 | 400 x 400 | 450 x 450 8 | Square…
- Table 4.2.13d Maximum stump height (mm): stump supporting single storey timber floor and metal roofStump material | Section size (mm) | Floor load area (m2) | Roof load area (m2) 0 | 6 | 12 Concrete f’c= 20 MPa | 100 x 100 | 3 | 2500 | 2000 | 1750…
- Table 4.2.13e Maximum stump height: stump supporting single storey tiled floor and tiled roofStump material | Section size (mm) | Floor load area (m2) | Roof load area (m2) 0 | 6 | 12 Concrete f’c = 20 MPa | 100 x 100 | 3 | 2250 | 1750 |…
- Table 4.2.13f Maximum stump height: stump supporting double storey timber floor and metal roofStump material | Section size (mm) | Floor load area (m2) | Roof load area (m2) 0 | 6 | 12 Concrete f’c = 20 MPa | 100 x 100 | 3 | 1750 | 1500 |…
- Table 4.2.13g Minimum dimensions of circular and square pad footings for clad frame, Class A and S sitesEffective supported areas (m2) | Width of square pad (mm) | Width of circular pad (mm) | Thickness (t) (mm) | Depth (mm) 10 | 400 | 500 | 200 | 400…
- 4.2.13 Stump footing detailsFootings for stumps must comply with— the provisions of Tables 4.2.13a, 4.2.13b or 4.2.13c for Class A and Class S sites; or the appropriate…
- Table 4.2.14a Reinforcement for stiffened raft footings for Class A sitesType of construction | Depth (D) (mm) | Bottom reinf. | Max. spacing c/l to c/l | Slab fabric Clad frame | 300 | 3-L8TM | N/A | SL72 Articulated…
- Table 4.2.14b Reinforcement for stiffened raft footings for Class S sitesType of construction | Depth (D) (mm) | Bottom reinf. | Max. spacing c/l to c/l | Slab fabric Clad frame | 300 | 3-L8TM | N/A | SL72 Articulated…
- Table 4.2.14c Reinforcement for stiffened raft footings for Class M sitesType of construction | Depth (D) (mm) | Bottom reinf. | Max. spacing c/l to c/l | Slab mesh Clad frame | 300 | 3-L11TM | 6.0Note 2 | SL72…
- 4.2.14 Stiffened rafts Class A, S and M sitesFooting and stiffened raft slabs must comply with— For Class A and S sites — Tables 4.2.14a, 4.2.14b and Figure 4.2.14a; and For Class M sites —…
- Table 4.2.15a Dimensions and reinforcement for strip footing systems for Class A sitesType of construction | D (mm) | B (mm) | Reinforcement (top and bottom) Clad frame | 300 | 300 | 3–L8TM Articulated masonry veneer | 300 | 300 |…
- Table 4.2.15b Dimensions and reinforcement for strip footing systems for Class S sitesType of construction | D (mm) | B (mm) | Reinforcement (top and bottom) Clad frame | 400 | 300 | 3–L8TM Articulated masonry veneer | 400 | 300 |…
- Table 4.2.15c Dimensions and reinforcement for strip footing systems for Class M sitesType of construction | D (mm) | B (mm) | Reinforcement (top and bottom) Clad frame | 400 | 300 | 3-L11TM Articulated masonry veneer | 450 | 300 |…
- 4.2.15 Strip footings Class A, S and M sitesStrip footings for Class A, S and M sites must comply with— for Class A and S sites — Tables 4.2.15a, 4.2.15b and Figure 4.2.15a; and for Class M…
- 4.2.16 Footing slabs for Class A sitesFooting slabs for Class A sites supporting the following external wall types must comply with Figure 4.2.16: Clad frame. Articulated masonry.…
- Table 4.2.17a Equivalent wall construction: single leaf masonryActual construction: external walls | Actual construction: internal walls | Equivalent wall construction Reinforced single leaf masonry |…
- Table 4.2.17b Equivalent wall construction: mixed constructionActual construction: external walls | Actual construction: internal walls | Equivalent wall construction Full masonry | Framed | Articulated full…
- Table 4.2.17c Equivalent wall construction: earth wall constructionActual construction: external walls | Actual construction: internal walls | Equivalent wall construction Infill panels of earth wall construction |…
- 4.2.17 Footings for single leaf masonry, mixed construction and earth wall constructionFootings supporting the following external wall types must comply with the equivalent wall construction set out in Tables 4.2.17a, 4.2.17b and…
- 4.2.18 Footings for fireplaces on Class A and S sitesFireplaces on Class A and S sites must be supported on a pad footing— 150 mm thick for single storey (one trafficable floor and a wall height not…
- 4.2.19 Shrinkage controlWhere brittle floor coverings, such as ceramic tiles, are to be used over an area greater than 16 m2, one of the following additional measures must…
- Table 4.2.20a Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = 0 m2Localised thickening | Maximum floor load area (m2) 4 | 10 | 16 Square thickening size (mm) | 450 x 450 | 650 x 650 | 850 x 850 Thickening depth…
- Table 4.2.20b Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = maximum 9 m2Localised thickening | Maximum floor load area (m2) 4 | 10 | 16 Square thickening size (mm) | 650 x 650 | 800 x 800 | 950 x 950 Thickening depth…
- Table 4.2.20c Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = maximum 18 m2Localised thickening | Maximum floor load area (m2) 4 | 10 | 16 Square thickening size (mm) | 750 x 750 | 900 x 900 | 1000 x 1000 Thickening depth…
- Table 4.2.20d Localised thickening under concentrated load — timber floor and metal roof — roof load area = 0 m2Localised thickening | Maximum floor load area (m2) 4 | 10 | 16 Square thickening size (mm) | 400 x 400 | 600 x 600 | 750 x 750 Thickening depth…
- Table 4.2.20e Localised thickening under concentrated load — timber floor and metal roof — roof load area = maximum 9 m2Localised thickening | Maximum floor load area (m2) 4 | 10 | 16 Square thickening size (mm) | 500 x 500 | 700 x 700 | 800 x 800 Thickening depth…
- Table 4.2.20f Localised thickening under concentrated load — timber floor and metal roof — roof load area = maximum 18 m2Localised thickening | Maximum floor load area (m2) 4 | 10 | 16 Square thickening size (mm) | 600 x 600 | 750 x 750 | 850 x 850 Thickening depth…
- 4.2.20 Concentrated loadsWhere a footing or slab supports a concentrated load from a structural steel column, localised thickening must— be provided in accordance with— for…
- 4.2.21 Minimum edge beam dimensionsFor footing slabs, the width of the edge beam at the base of the rebate must not be less than 200 mm, except that if R10 or N10 ties at 900 mm…
- 4.2.22 Recessed areas of slabsWhere a recess in a slab is provided, it must comply with one of the following: For recess depths less than or equal to half the nominal slab…