Housing Provisions clause · ABCB Housing Provisions 2022

5.4.2 External walls

Part 5.4 Unreinforced single leaf masonry

Open 5.4.2 on NCC Online ↗

(1) Single leaf unreinforced masonry walls with engaged piers and return walls must comply with the relevant provisions of this Part and be constructed in accordance with the following:

The roof frame must be connected continuously to the top of the wall (see Figure 5.4.2a).

Stack bonded piers must have wall ties at every fourth course.

Pier and return supports size limitations for—

single leaf unreinforced masonry walls with engaged piers, must comply with Table 5.4.2a and Figure 5.4.2b; and

single leaf unreinforced masonry walls with return supports, must comply with Table 5.4.2b and Figure 5.4.2c.

An engaged pier or return wall must be provided at both sides of an opening.

The width of an opening must be not more than the spacing between the engaged piers unless the engaged piers either side of the opening are designed in accordance with AS 3700.

Articulation joints must be located within 300 mm of vertical supports in accordance with 5.6.8.

(2) A Class 10a building containing not more than 1 storey may be enclosed with single leaf masonry external walls not less than 90 mm in thickness, provided that—

the building measured in the direction of the span of the roof is not more than 9 m and the height is not more than 2.7m; and

engaged piers are provided that are in accordance with Tables 5.4.2c and 5.4.2d; and

the roof does not place any spreading thrust onto the external walls; and

the Class 10a building is located in an area with a wind class of not more than N2.

Table 5.4.2a Engaged piers in external single leaf masonry walls to AS 3700

Element

Symbol used in Figure 5.4.2b

Thickness of wall (T)

90

110

Pier size (minimum) (not more than N2)

A x B

290 x 190 (800 spacing)

350 x 230 (1150 spacing)

Pier size (minimum) (not more than N3)

A x B

290 x 290 (700 spacing)

350 x 350 (1050 spacing)

Spacing of returns (maximum)

S

700

1050

Height (maximum)

H

2400

2700

Table Notes

Dimensions are in mm.

Return supports are not required for 140 mm and 190 mm thick walls.

Table 5.4.2b Return support limitations for external single leaf masonry walls to AS 3700

Element

Symbol used in Figure 5.4.2c

Thickness of wall (T)

90

110

140

190

Return length (minimum)

R

450

450

–

–

Spacing of returns (maximum) (N2)

S

1050

1300

–

–

Spacing of returns (maximum) (N3)

S

600

750

–

–

Height (maximum)

H

2400

2400

1700 (N2)

2300 (N2)

Table Notes

Dimensions are in mm.

Return supports are not required for 140 mm and 190 mm thick walls.

Table 5.4.2c Engaged piers in external walls of Class 10a buildings — wall height: 2.4 m

Wall thickness (mm)

Pier thickness (mm)

Pier width (mm)

Spacing (mm) for wind class

N1

N2

90

190

290

1000

600

90

290

190

1700

1200

90

290

290

2600

1800

110

230

230

1320

840

110

230

350

2040

1320

110

350

230

3240

2160

110

350

350

4920

3360

Table 5.4.2d Engaged piers in external walls of Class 10a building — wall height: 2.7 m

Wall thickness (mm)

Pier thickness (mm)

Pier width (mm)

Spacing (mm) for wind class

N1

N2

90

190

290

700

500

90

290

190

1300

900

90

290

290

2000

1400

110

230

230

960

600

110

230

350

1440

960

110

350

230

2520

1680

110

350

350

3840

2520

Figure 5.4.2a Top lateral restraint detail for unreinforced single leaf masonry walls

Figure Notes

Tie down of wall must comply with 5.6.6.

Figure 5.4.2b Engaged piers in external single leaf masonry walls to AS 3700

Figure 5.4.2c Return support limitations for external single leaf masonry walls to AS 3700

Tables

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 5.4.2.