5.6.8 Vertical articulation joints
Part 5.6 Masonry components and accessories · NCC 2019: 3.3.5.13
(1) Vertical articulation joints must be provided in masonry walls in accordance with (2), except in walls constructed on sites where the soil classification is A or S (see 4.2.2).
(2) Articulation joints between masonry elements must have a width of not less than 10 mm and be provided (see Figures 5.6.8a and 5.6.8b)—
in straight, continuous walls with openings less than 900 mm x 900 mm or walls without openings — at not more than 6 m centres and within 4.5 m, but not closer than 470 mm of all corners; and
in straight, continuous walls with openings more than 900 mm x 900 mm — at not more than 5 m centres and located so that they are not more than 1.2 m away from openings; and
where the height of the wall changes by more than 20% — at the position of change in height; and
where a wall changes in thickness; and
at control or construction joints in footings or slabs; and
at junctions of walls constructed of different masonry materials.
(3) Articulation joints must not be located adjacent to arched openings.
(4) Articulation joints must be filled with flexible sealant that is supported during installation by—
a compressible foam or polystyrene filler (see Figures 5.6.8d and 5.6.8e); or
a purpose made backer rod (see Figures 5.6.8c, 5.6.8d, 5.6.8e and 5.6.8f).
Figure 5.6.8a Example of vertical articulation joint locations in plan view
Figure 5.6.8b Vertical articulation joints
Figure 5.6.8c Articulation joint with backer rod and sealant—single skin masonry and masonry veneer walls
Figure 5.6.8d Articulation joint in unreinforced single leaf masonry wall with compressed foam
Figure 5.6.8e Articulation joint in unreinforced masonry veneer wall with compressed foam
Figure 5.6.8f Articulation joint in cavity masonry wall
Changed in NCC 2025. See ABCB Housing Provisions 2025 5.6.8, or show what changed.
(1) Vertical articulation joints must be provided in masonry walls … provided (see Figures 5.6.8a and 5.6.8b)— in straight, continuous walls without openings or with openings less not more than 900 mm x 900 mm or walls without openings — at not more than 6 m centres and within 4.5 m, but not closer than 470 mm mm, of all corners; and in straight, continuous walls with openings … joints Figure 5.6.8c Articulation joint with backer rod and sealant —single — single skin masonry and masonry veneer walls Figure 5.6.8d Articulation joint … compressed foam Figure 5.6.8f Articulation joint in cavity masonry wall