Housing Provisions clause · ABCB Housing Provisions 2025

5.6.8 Vertical articulation joints

Part 5.6 Masonry components and accessories · NCC 2019: 3.3.5.13

Open 5.6.8 on NCC Online ↗

(1) Vertical articulation joints must be provided in masonry walls in accordance with (2), except in walls constructed on sites where the soil classification is A or S (see 4.2.2).

(2) Articulation joints between masonry elements must have a width of not less than 10 mm and be provided (see Figures 5.6.8a and 5.6.8b)—

in straight, continuous walls without openings or with openings not more than 900 mm x 900 mm — at not more than 6 m centres and within 4.5 m, but not closer than 470 mm, of all corners; and

in straight, continuous walls with openings more than 900 mm x 900 mm — at not more than 5 m centres and located so that they are not more than 1.2 m away from openings; and

where the height of the wall changes by more than 20% — at the position of change in height; and

where a wall changes in thickness; and

at control or construction joints in footings or slabs; and

at junctions of walls constructed of different masonry materials.

(3) Articulation joints must not be located adjacent to arched openings.

(4) Articulation joints must be filled with flexible sealant that is supported during installation by—

a compressible foam or polystyrene filler (see Figures 5.6.8d and 5.6.8e); or

a purpose made backer rod (see Figures 5.6.8c, 5.6.8d, 5.6.8e and 5.6.8f).

Figure 5.6.8a Example of vertical articulation joint locations in plan view

Figure 5.6.8b Vertical articulation joints

Figure 5.6.8c Articulation joint with backer rod and sealant — single skin masonry and masonry veneer walls

Figure 5.6.8d Articulation joint in unreinforced single leaf masonry wall with compressed foam

Figure 5.6.8e Articulation joint in unreinforced masonry veneer wall with compressed foam

Figure 5.6.8f Articulation joint in cavity masonry wall

Changed since NCC 2022. See ABCB Housing Provisions 2022 5.6.8, or show what changed.

(1) Vertical articulation joints must be provided in masonry walls … provided (see Figures 5.6.8a and 5.6.8b)— in straight, continuous walls without openings or with openings less not more than 900 mm x 900 mm or walls without openings — at not more than 6 m centres and within 4.5 m, but not closer than 470 mm mm, of all corners; and in straight, continuous walls with openings … joints Figure 5.6.8c Articulation joint with backer rod and sealant —single — single skin masonry and masonry veneer walls Figure 5.6.8d Articulation joint … compressed foam Figure 5.6.8f Articulation joint in cavity masonry wall