9.2.10 Roof lights
Part 9.2 Fire separation of external walls · NCC 2019: 3.7.2.8
Combustible roof lights, skylights or the like installed in a roof or part of a roof required to have a non-combustible covering must—
have an aggregate area not more than 20% of the roof or part of the roof; and
be not less than—
900 mm from the allotment boundary other than the boundary adjoining a road alignment or other public space; and
1.8 m from any roof light or the like in another building on the allotment other than an associated building or a detached part of the same building (see Figure 9.2.10).
Figure 9.2.10 Location of combustible roof lights
Figure Notes
Roof lights depicted in Figure 9.2.10 are combustible.