Housing Provisions clause · ABCB Housing Provisions 2025

9.2.10 Roof lights

Part 9.2 Fire separation of external walls · NCC 2019: 3.7.2.8

Open 9.2.10 on NCC Online ↗

Combustible roof lights, skylights or the like installed in a roof or part of a roof required to have a non-combustible covering must—

have an aggregate area not more than 20% of the roof or part of the roof; and

be not less than—

900 mm from the allotment boundary other than the boundary adjoining a road alignment or other public space; and

1.8 m from any roof light or the like in another building on the allotment other than an associated building or a detached part of the same building (see Figure 9.2.10).

Figure 9.2.10 Location of combustible roof lights

Figure Notes

Roof lights depicted in Figure 9.2.10 are combustible.

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 9.2.10.

Defined terms used