9.2.3 Construction of external walls
Part 9.2 Fire separation of external walls · NCC 2019: 3.7.2.4
(1) An external wall (including a gable) required to be fire-resisting (referred to in 9.2.1 or 9.2.4) must—
commence at the footings or ground slab, except where the external wall commences above a separating wall complying with 9.3.1 (see Figure 9.2.2e); and
extend to—
the underside of a non-combustible roof covering, except that a wall may terminate not more than 200 mm from the underside of a non-combustible roof covering, where the area between the external wall and underside of the roof covering is sealed with a non-combustible fascia, gutter or flashing; or
the underside of a non-combustible eaves lining (See Figures 9.2.3a and b); and
be constructed in accordance with (2).
(2) A wall required by (1) must—
have an FRL of not less than 60/60/60 when tested from the outside; or
be of masonry-veneer construction in which the external masonry veneer is not less than 90 mm thick; or
be of masonry construction not less than 90 mm thick.
(3) Openings in external walls required to be fire-resisting (referred to in 9.2.1 or 9.2.4) must be protected by—
non-openable fire windows or other construction with an FRL of not less than –/60/–; or
self-closing solid core doors not less than 35 mm thick.
(4) The requirements of (3) do not apply to a window in a non-habitable room that is located adjacent to and not less than 600 mm from the boundary of an adjoining allotment or 1.2 m from another building on the same allotment provided that—
in a bathroom, laundry or toilet, the opening has an area of not more than 1.2 m2; or
in a room other than one referred to in (a), the opening has an area of not more than 0.54 m2 and—
the window is steel-framed, there are no opening sashes and it is glazed in wired glass; or
the opening is enclosed with translucent hollow glass blocks.
(5) Subfloor vents, roof vents, weepholes, control joints, construction joints and penetrations for pipes, conduits and the like need not comply with (3).
Figure 9.2.3a Typical construction of external walls
Figure Notes
The external wall is deemed to extend to the underside of non-combustible roof covering, or non-combustible eaves lining, when constructed as shown.
Where sarking is installed it must be located so that ponding of water is avoided between the fascia and the first roofing batten.
The location of flashing and framing is indicative only.
Masonry shown in diagram (b) is to be terminated in accordance with 9.2.3(1)(b).
Figure 9.2.3b Typical construction of external walls — attached Class 1 buildings on the same allotment
Figure Notes
The external wall is deemed to extend to the underside of non-combustible roof covering, or non-combustible eaves lining, when constructed as shown.
Where sarking is installed it must be located so that ponding of water is avoided between the fascia and the first roofing batten.
The location of flashing and framing is indicative only.
Masonry shown in diagram (b) is to be terminated in accordance with 9.2.3(1)(b).